PARTS OF THE METER
FRONT OF THE METER
Figure 5-1 shows each part of the front of the meter. Table 5-1 on the next page gives a brief description of each part.

1
- Setpoint 1 Status
2 - Setpoint 2 Status
Front-Panel Illustration
Figure 5-1. Front-Panel Illustration

Front-Panel Part Description Table 5-1
1
-1.9.9.9. or 9.9.9.9.
4-digit 14 segment, 0.54" high LED display with programmable decimal point.
2
SETPOINT LED
These LEDs labeled 1 and 2 display the status of setpoints 1 and 2.
3
SETPTS BUTTON
This button functions only in the run mode. When the meter is in the run mode, press this button to sequentially recall the previous setpoint settings. After using the /MAX and /DEV buttons to alter these settings as desired, press the SETPTS button to store these new values.

Unless you press the SETPTS button within 20 seconds to store your input, the meter will scroll to setpoint 2 and retain the last value stored.

NOTE: If the dual relay option is not installed, pressing the SETPTS button will display "V.-03" which is the meter's software version.
4
/MAX BUTTON
During the run mode, press the /MAX button to recall the PEAK reading since the last press of the RESET button. To return to the current readings without resetting the PEAK reading, press the /MAX button. To reset the PEAK reading, press the RESET button.

During the configuration mode, use the /MAX button to change the values of the flashing digit shown on the display and/or toggle between menu choices, such as "R.1=F" or "R.1=C". When configuring your setpoint values, press the /MAX button to increment the flashing digit from 0 to 9 by 1's.
5
/DEV BUTTON
During the run mode press the /DEV button to display the deviation from setpoint 1.
When configuring your setpoint values, press the /DEV button to scroll to the next digit.
6
MENU BUTTON
In the run mode, press the MENU button to terminate the current measuring process and enter you into the configuration mode


In the configuration mode, press the MENU button to store changes in the non-volatile memory and then advance you to the next menu item.
7
RESET BUTTON
If you hard reset or power off/on the meter, it shows "RST", followed by "RTDS".

In the run mode, press the RESET button to reset the setpoints and display "SP.RS". If display shows peak value, press the RESET button to reset peak value. Display shows "PK.RS".

In the configuration mode, press the RESET button once to review the previous menu. Pressing the RESET button twice results in a hard reset and returns you to the run mode.

REAR OF THE METER
Figure 5-2 shows the connector label mounted at the top of the meter housing. Table 5-2 gives a brief description of each connector at the rear of the meter.

Connectors Label
Figure 5-2. Connectors Label

Rear Connector Description Table 2-2
CONNECTOR
DESCRIPTION
TB1-1
Setpoint 1: Normally open (N.O.1) connection
TB1-2
Setpoint 1: Normally closed (N.C.1) connection
TB1-3
Setpoint 1: Common 1(COM1) connection
TB1-4
Setpoint 2: Normally open (N.O.2) connection
TB1-5
Setpoint 2: Normally closed (N.C.2) connection
TB1-6
Setpoint 2: Common 2(COM2) connection
TB1-7
AC Line connection (no connection on DC powered units)
TB1-8
AC Neutral connection (+ Input on DC powered units)
TB1-9
AC ground (-DC power return on DC powered units)
TB1-10
Analog 1 voltage output
TB1-11
Analog 2 current output
TB1-12
Analog 3 Return
TB2-1
No Connection
TB2-2
+E: Positive excitation (current source)
TB2-3
No Connection
TB2-4
+R: For 3 or 4 wire RTD connection
TB2-5
No Connection
TB2-6
+S: Positive signal input
TB2-7
-S: Negative signal input
TB2-8
-R: For 2 wire RTD connection